Item |
Specifications |
Power input
|
Rated input voltage |
Grade of rated voltage is 220V or 380V: voltage continued fluctuation±10%, brief fluctuation:-15~+10%, voltage imbalance rated<3%, aberration rate meet IEC61800-2 requirements. |
Rated input current |
Refer to table 2-1 |
Rated frequency |
50/60Hz, fluctuation range ±5% |
Power output
|
Standard adaptive motor |
Refer to table 2-1 |
Rated capacity |
Refer to table 2-1 |
Rated current |
Refer to table 2-1 |
Output voltage |
Output three-phase under the rated input condition, 0V~rated input voltage, error is less than±3%. |
Main Control Functions
|
Highest frequency |
50.00Hz~600.00Hz |
Carrier frequency |
0.5kHz~16.0kHz, auto-adjust carrier frequency. |
Input frequency resolution |
0.01Hz (digit setup mode) |
Control mode |
Open vector, closed vector, V/F control |
Start torque |
0.25Hz/150% (vector) |
Motor type |
Asynchronous motor |
Speed range |
02:40 |
Speed control accuracy |
±0.2% |
Torque control accuracy |
5% |
Overload capacity |
G type motor: 150% rated current for 60sec; 200% rated current for 1sec. P type motor: 120% rated current for 60sec; 150% rated current for 5sec. |
Torque boost |
Auto torque boost, manual torque boost by 0.1%~10.0%. |
Acceleration / deceleration curve |
Linear or S curve acceleration/deceleration mode, 4 types of acceleration/deceleration time, range 0.0s~6500.0s. |
DC braking |
DC braking frequency: 0.00Hz~max output frequency, braking time: 0.0s~100.0s, braking current: 0.0%~100.0%. |
Jogging control |
Jogging frequency range: 0.00Hz~max output frequency, jog acceleration/deceleration time 0.0s~6500.0s. |
Main Control Functions
|
Easy PLC, multi-stage speed run |
Via built-in PLC or control terminal can realize max 16 stage speed run. |
Built-in PID |
Can realize process control conveniently. |
Auto-adjustment of the voltage |
Can keep the output voltage constant automatically when the grid voltage changed. |
Dynamic over voltage suppression |
Auto suppress energy feedback value while run frequency changes, prevent bus over current tripping off. |
Oscillation suppression |
Optimize V/F oscillation arithmetic, realize V/F steady operation. |
Individual Function
|
Power dip ride through |
It ensures that the AC drive continues to run for a short time when an instantaneous power failure or sudden voltage reduction occurs. |
Timing control |
Timing control function: setting time range: 0min-6500.0min. |
Multi-motor switchover |
Two motors can be switched over via two groups of motor parameters. |
Support extension |
Support multi-function I/O extension card and MFI port related expansion function components defined by the manufacturer. |
Operation
|
Running command source |
Operation panel, control terminals, serial communication port, you can perform switchover between these sources in various ways. |
Frequency source |
There are a total of 11 frequency sources, such as digital setting, analog voltage setting, analog current setting, pulse setting and serial communication port setting, panel potentiometer setting, you can perform switchover between these sources in various ways. |
Auxiliary frequency source |
There are 11 auxiliary frequency sources, it can implement fine tuning of auxiliary frequency and frequency synthesis. |
Input terminal |
6 digit terminal input, 1 terminal support rapid pulse input on max 100kHz. 2 analog input terminals; with optional 0/4mA to 20mA current input or 0V to 10V voltage input. Extension capacity: 3 digital input terminals and 1 analog input terminals. |
Output terminal |
2 analog output terminals; with optional 0/4mA to 20mA current output or -10V to 10V voltage output. 2 digit output terminals; one supporting 0.01KHz~100KHz square signal rapid pulse output. 2 relay output terminal Extension capacity: 1 digit output terminal. |
Display and Keypad Operation |
LED display |
Can display 5 parameters |
Display and Keypad Operation |
Protection function |
Motor short-circuit detection at power-on, input/output phase loss protection, overcurrent protection, overvoltage protection, undervoltage protection, overheat protection and overload protection etc. |
Environment
|
Installation location |
Indoor, free from direct sunlight, without dust, corrosive gas, combustible gas, oil smoke, vapor, drip or salt etc. |
Altitude level |
Lower than 2000m (de-rate if altitude is higher than 2000m). |
Ambient temperature |
-10℃-+40℃ (de-rate if the ambient temperature is between 40℃ and 50℃). |
Humidity |
<95%RH, without condensing.. |
Vibration |
<5.9m/s2 (0.6g) |
Storage temperature |
-20℃- +60℃ |
Protection grade |
IP20 |
Cooling method |
Forced air cooling |