Input Type
|
Thermocouple
|
K, J, T, R, N, S, B (Input Resistance: 1M Ω )
|
Thermocouple /
R.T.D. Input, Current / Voltage Input are switchable with the front key.
|
R.T.D.
|
Pt100, JPt100 (provided that the external resistance is below 10 Ω (per wire) and 3 wires have all the same resistance)
|
Current / Voltage
|
4 - 20mADC (Input Resistance 250 Ω ), 0 - 5 VDC / 1 - 5 VDC (Input Resistance above 500k Ω ) (Measured Current Appx. 2mA)
|
Indication
|
PV Character
|
4-digits White 10mm height (7.6mm height for TTM-002W, 14mm height for TTM-006W / 009W)
|
SV Set Value
|
4-digist Green 8mm height (5.25mm height for TTM-002W)
|
Various Function
|
LED: Red (AL1, AL2, OUT1, OUT2, RDY), LED: Green (COM, DI), COM for TTM-002W is at 1st decimal digit of display.
|
Control Method
|
PID
Auto-Tuning Self-Tuning
|
Proportional band (P1)
|
0.1 to 200.0% of the setting limiter span
|
Proportional band (P2) at Output 2 side.
|
0.10 to 10.00 times (magnification over the proportional band P1)
|
Integral Time (I)
|
0 to 3600 sec. (Integral Control Action becomes OFF at 0).
|
Derivative Time (D)
|
0 to 3600 sec. (Derivative Action becomes OFF at 0).
|
Proportional Cycle (T1, T2)
|
1 to 120 sec.
|
Dead Band (DB)
|
Temp. Input
|
-100.0 to +100.0 or -100 to +100(℃ )
|
Analogue Input
|
-1000 to 1000 (digit) (Decimal point is at designated place)
|
ON / OFF
|
Control Sensitivity (C1, C2)
|
Temp. Input
|
0 to 999 or 0.0 to 999.9(℃ )
|
Analogue Input
|
0 to 9999 (digit) (Decimal point is at designated place)
|
OFF point of Output 1 & 2
|
Position Setting
|
Temp. Input
|
-199 to 999 or -199.9 to 999.9(℃ )
|
Analogue Input
|
-1999 to 9999 (digit) (Decimal point is at designated place)
|
Control Output
|
Relay Contact
|
250VAC, 3A (Resistance Load) 1a contact (On heating / cooling operation, output 2 is 250VAC, 2.4A (Load Resistance) 1a contact)
|
SSR Drive Voltage
|
0 to 12VDC (Load Resistance: 600 Ω or more)
|
Current
|
4 to 20mADC (Load Resistance: Below 600 Ω )
|
Sampling Time
|
0.25 sec. (Output change cycle is also the same)
|
Setting and Indication Accuracy
|
Thermocouple
|
± (0.3% + 1-digit) of input value or ± 2℃ , whichever is bigger (Ambient Temp.: 23℃± 10℃ ) However -99 to 0℃ : ± 3℃ -210 to -100℃ : ± 4℃ Thermocouple B under 400℃ is not regulated.
|
R.T.D.
|
± (0.3% + 1-digit) of input value or ± 0.9℃ , whichever is bigger (Ambient Temp.: 23℃± 10℃ )
|
Current (4-20mA), Voltage (0 - 5VDC, 1 - 5VDC)
|
± (0.3% + 1-digit) of setting value limiter span (Ambient Temp.: 23℃± 10℃ )
|
Memory Element
|
EEPROM
|
Input Voltage
|
100 - 240VAC (-15%, +10%) or 24V AC/DC ( ± 10%) 50/60Hz * For transfer output models, 24V AC/DC is not selectable.
|
Weight
|
TTM-002W / 004W: below 180gms., TTM-005W / 006W: below 300gms., TTM-007W: below 250gms., TTM-009W: below 380gms.
|
Power Consumption
|
10VA (264VAC), 6VA (24VAC), 4W (24VDC)
|
Accessories
|
Instruction Manual & mounting attachment (TTM-002W, 004W), metal mounting bracket (TTM-005W, 006W, 007W, 009W)
|
Suitable Operating Environment
|
0 to 50℃ , 20 to 90% RH (no condensation)
|
Suitable Storage Environment
|
-25℃ to 70℃ , 5 to 95% RH (no icing and condensation)
|
Functions
|
Manipulated Variable Limiter (ML1, MH1, ML2, MH2)
|
0.0 (-10.0) to 100.0 (110.0)% Values indicated in ( ) are for current / voltage models.
|
Set Limiter (SLL, SLH)
|
See "Input & Scale Range Table".
|
Selectable Control Mode(CNT)
|
Auto-Tuning PID Type A (Normal / Reverse Action), Auto-Tuning PID Type B (Normal / Reverse Action), Self-Tuning PID (Normal / Reverse Action), ON / OFF (Normal / Reverse Action)
|
PV Correction 0-point Setting (PVS)
|
Thermocouple / R.T.D.: -199 to 999 or -199.9 to 999.9 (℃ ) Current / Voltage (Decimal point at designated position): -1999 to 9999 (digit)
|
PV Correction Gain Setting
|
0.50 to 2.00 (times)
|
Input Filter
|
0.0 to 99.9 (sec.)
|
Manual Reset (PBB)
|
0.0 to 100.0%, -100.0 to +100.0 (heating / cooling) of proportional band.
|
Timer Operation Mode (TMM)
|
0 min. 00 sec. to 59 min. 59 sec. 0 hr. 00 min. to 99 hrs. 59 min. Accuracy: ± (1.5%+0.5 sec.) of the set time.
|
Decimal Point Shift (DP)
|
Indication after the decimal point Yes / No
|
Manual Control
|
Manual control is possible (Balanceless / Bumpless)
|
RUN / READY
|
RUN / READY is switchable
|
Blind Function
|
A non-indication is possible for any unnecessary parameter screen.
|
Auto-Tuning (AT) Coefficient
|
A coefficient can be set to the proportional band which is computed by the Auto-Tuning.
|
FUNC Key
|
Selectable from "Digit Shift", "AT", "RUN / READY", "Timer Start / Reset".
|
Priority Display
|
Selected parameter screen can be displayed in the operation mode (9-points)
|
Lock Function (LOC)
|
4-modes (OFF, ALL, Operation Mode Lock, Lock except Operation Mode)
|
Self-Checking Function
|
EEPROM Data Check (Err0), A/D Converter Operation Check (Err1), Auto-Tuning Check (Err2), Built-In Watchdog Timer
|
Ramp Function
|
Operation: When the SV is changed, it sets the SV changes per minute.
The setting can be done individually for SV & SV2 respectively.
*SV2 is available when option DI is selected.
Setting Range: 0.0 to 999.9
The ramp function is disabled by 0.0 setting.
Setting Unit: 0.1℃ /min. (thermocouple / R.T.D. input model)
0.1-digit/min. of SV setting unit (analogue input model)
|
External Standard
|
6 substances as restricted by the RoHS Directives are not used.
|
Lead: Below 1,000 ppm Mercury: Below 1,000 ppm Cadmium: Below 100 ppm Hexad Chrome: Below 1,000 ppm Polybrominated Biphenyl (PBB): Below 1,000 ppm
Polybrominated Diphenyl Ethers (PBDE): Below 1,000 ppm
|
UL/cUL/CE Markings (except TTM-002W)
|