thông số kỹ thuật đồng hồ nhiệt độ TTM-i4N-R-AB

* Large white display for clear vi" />thông số kỹ thuật đồng hồ nhiệt độ TTM-i4N-R-AB

* Large white display for clear vi " />

TTM-i4N-R-AB Bộ điều khiển nhiệt độ Toho Size  48 × 48mm
TTM-i4N-R-AB Bộ điều khiển nhiệt độ Toho Size  48 × 48mmTTM-i4N-R-AB Bộ điều khiển nhiệt độ Toho Size  48 × 48mm

TTM-i4N-R-AB Bộ điều khiển nhiệt độ Toho Size 48 × 48mm

Đã xem : 109 | Đã mua : 0
0/0 Đánh giá | Viết đánh giá
1,488,240₫
Còn hàng
Mã sản phẩm: TTM-i4N-R-AB

* Equipped with ultra-fuzzy control.

* By connecting the loader cable, parameter setting would be possible without the external power supply (power will be supplied from the PC).

Even the complicated setting can easily be done with the simple key operation of the PC. The setting procedures are greatly minimized.

* Sampling cycle︓250mS.

* Fuzzy control︓Effectively prevents the“OverShoot”

better than the normal PID Control at the initial start-up stage.

+
 
 

Sản phẩm cùng loại

Chi tiết sản phẩm Đồng hồ nhiệt TTM-i4N-R-AB

Hãng sản xuất Toho

Chi tiết Đồng hồ nhiệt độ TTM-i4N-R-AB

■ TEMPERATURE INPUT SECTION

Input types

Thermocouple:K, J, R, T, N, S, B (JIS C 1602-1995) RTD Pt100, JPt100 (JIS C 1604-1997)

The input types are switched by setting.

Sampling cycle

250mS

 

Display precision: (the ambient temperature 23±10°C)

Thermocouple:Input value ±(0.3% + 1 digit) or ±2°C, whichever is larger (the ambient temperature 23±10°C).However, the condition shall be ±3°C in the -100 to 0°C range, and

±4°C in the -200 to -100°C range. Not specified for temperatures not higher than 400°C for thermocouple B.

RTD Input value ±(0.3% + 1 digit) or 0.9°C, whichever is larger (the ambient temperature 23±10°C).

At ambient temperatures of 0 to 50°C, ±(0.5% + 1 digit) or 1.5°C, whichever the higher.

■ CONTROL OUTPUT 

Relay contact

output

Control  output:250VAC,  3A  (resistance  load) Contact 1a Minimum load 5VDC, 100mA

Event  1  output:250VAC,  2.4A  (resistance  load) Contact 1a Minimum load: 5VDC, 10mA

SSR driving voltage output

 

Control output:12VDC Load resistance: 600 or more

■ TIMER 

Unit setting

Switchover between hours/minutes and minutes/seconds

Setting range

0 minutes and 0 seconds to 59 minutes 59 seconds

0 hours 0 minutes to 99 hours 59 minutes

Setting precision

Time setting ± (1.5% + 0.5 seconds)

■ GENERAL SPECIFICATION

Power supply voltage

100 to 240VAC, 50/60Hz

 

 

Envi r onment al condi t i ons

Standard environmental conditions

Temperature range: 23°C ±10°C

Humidity range: 45 to 75%RH

Operating environmental conditions

Temperature range: 0 to 50°C

Humidity range: 20 to 90%RH (no condensation)

Storage environmental

conditions

Temperature range: -25 to 70°C (no freezing, no condensation)

Humidity range: 5 to 95%RH (non-condensing)