Parameter
|
Operation description
|
|
Parameter
|
Operation description
|
|
- POWER ON DELAY
- uses 1 set time (set time displayed on SV display)
- when power is applied, output turns OFF, timing starts ● when displayed time reaches set time, output turns ON, displayed time is held (ONE-SHOT output selectable)
|
|
- SIGNAL ON DELAY
- uses 1 set time (set time displayed on SV display)
- when START signal is applied, timing starts (START signal holds ON status )● when displayed time reaches set time output turns ON, holds output and displayed time (ONE-SHOT output selectable)
- When START signal is cancelled, initializes output and displayed time
|
POND
|
SOND
|
|
- POWER ON FLICKER - OFF START
- uses 2 set times, Ton and Toff (Toff set time displayed on PV display, Ton set time displayed on SV display)
- when power is applied, OFF timing starts
- when displayed time reaches Toff set time, output turns ON, after displayed time initialization ON timing starts
- when displayed time reaches Ton set time, output turns OFF, after displayed time initialization OFF timing starts
- output repeats ON/OFF operations according to Ton and Toff set times
|
|
- SIGNAL ON FLICKER - OFF START
- uses 2 set times, Ton and Toff (Toff set time displayed on PV display, Ton set time displayed on SV display)
- when START signal is applied,OFF timing starts (START signal holds ON status) ● when displayed time reaches Toff set time, output turns ON, after displayed time initialization ON timing starts
- when displayed time reaches Ton set time output turns OFF, after displayed time initialization OFF timing starts
- output repeats ON/OFF operations according to Ton and Toff set times
- when START signal is cancelled, initializes output and displayed time
|
PFKF
|
SFKF
|
|
- POWER ON FLICKER - ON START
- uses 2 set times, Ton and Toff (Ton set time displayed on PV display, Toff set time displayed on SV display)
- when power is applied, output turns ON, ON timing starts● when displayed time reaches Ton set time output turns OFF, after displayed time initialization OFF timing starts
- when displayed time reaches Toff set time, output turns ON, after displayed time initialization ON timing starts
- output repeats ON/OFF operations according to Ton and Toff set times
|
|
- SIGNAL ON INTERVAL
- uses 1 set time (set time displayed on SV display)
- When START signal is applied, output turns ON, timing starts (START signal holds ON status )
- when displayed time reaches set time output turns OFF,displayed time is held
- When START signal is cancelled, initializes output and displayed time
|
SINT
|
|
- SIGNAL ON INTERVAL
- uses 1 set time (set time displayed on SV display)
- When START signal is applied, output turns ON, timing starts (START signal holds ON status )
- when displayed time reaches set time, output turns OFF, displayed time is held
- when START signal is cancelled, initializes output and displayed time
|
PFKN
|
SNFN
|
|
- POWER ON INTERVAL
- uses 1 set time (set time displayed on SV display)
- when power is applied, output turns ON, timing starts● when displayed time reaches set time, output turns OFF, displayed time is held
|
|
- SIGNAL ON/OFF DELAY - OFF START
- uses 2 set times, Ton and Toff (Ton set time displayed on PV display, Toff set time displayed on SV display)
- when START signal is applied, ON timing starts
- when displayed time reaches Ton set time output turns ON,displayed time is held
- When START signal is cancelled, output holds ON output status,OFF timing starts● when displayed time reaches Toff set time output turns OFF, displayed time is held
|
PINT
|
SNFF
|
|
- TWIN - ON START
- uses 2 set times, Ton and Toff (Ton set time displayed on PV display, Toff set time displayed on SV display)
- when power is applied, OUT1 output turns OFF, OUT2 output turns ON, ON timing starts
- when displayed time reaches Ton set time OUT1 output turns
ON, OUT2 output turns OFF, after displayed time initialization
OFF timing starts
- when displayed time reaches Toff set time, OUT1 output turns
OFF, holds output and displayed time
|
|
- SIGNAL OFF DELAY
- uses 1 set time (set time displayed on SV display)
- when START signal is applied, output turns ON (START signal holds ON status )
- when START signal is cancelled, holds output and timing starts
- when displayed time reaches set time output turns OFF, displayed time is held
- when START signal is cancelled, initializes output and displayed time
|
SOFD
|
|
- SIGNAL TRIGGER ON DELAY
- uses 1 set time (set time displayed on SV display)
- when START signal is applied, timing starts
- when displayed time reaches set time output turns ON, holds output and displayed time (ONE-SHOT output selectable)
- when START signal is repeatedly applied, only uses the first START signal
|
TWON
|
S.OND
|
|
- TWIN - OFF START
- uses 2 set times, Ton and Toff (Toff set time displayed on PV display, Ton set time displayed on SV display)
- when power is applied, OUT1 and OUT2 outputs turn OFF, OFF timing starts
- when displayed time reaches Toff set time, OUT2 output turns
ON, after displayed time initialization ON timing starts
- when displayed time reaches Ton set time, OUT1 output turns
ON, holds output and displayed time
|
|
- SIGNAL TRIGGER ON FLICKER - ON START
- uses 2 set times, Ton and Toff (Toff set time displayed on PV display, Ton set time displayed on SV display)
- when START signal is applied, output turns ON, ON timing starts
- when displayed time reaches Ton set time output turns OFF, after displayed time initialization OFF timing starts
- when displayed time reaches Toff set time, output turns ON, after displayed time initialization ON timing starts
- output repeats ON/OFF operations according to Ton and Toff set times
- When START signal is repeatedly applied, only uses the first START signal
|
TWOF
|
S.FKN
|
|
- STAR – DELTA
- uses 2 set times, Ton and Toff (Ton set time displayed on PV display, Toff set time displayed on SV display)
- when power is applied, OUT1 output turns OFF, OUT2 output turns ON, ON timing starts
- when displayed time reaches Ton set time, OUT2 output turns
OFF, after displayed time initialization OFF timing starts
- when displayed time reaches Toff set time, OUT1 output turns
ON, holds output and displayed time
- OUT1 operates as 'Δ' output, OUT2 operates as '' output.
- Toff set time is 'Δ - ' operation switching time
|
|
- SIGNAL TRIGGER ON INTERVAL
- uses 1 set time (set time displayed on SV display)
- when START signal is applied, output turns ON, timing starts
- when displayed time reaches set time output turns OFF, displayed time is held
- When START signal is repeatedly applied, only uses the first START signal
- after reaching set time, when START signal is applied, output turns ON, and after time value initialization timing starts
|
S.INT
|
|
- SIGNAL TRIGGER ON DELAY – RESET
- when START signal is applied, timing starts
- when displayed time reaches set time, output turns ON, holds output and displayed time (ONE-SHOT output selectable)
- when START signal is re-applied during timing, timing starts after displayed time initialization
|
S - D
|
S.ODR
|